Installation
Requirements |
1. |
A pressure reducing valve with bypass, must
be installed between the cold water inlet shut off valve and the expansion
tank. The valve must be adjusted to provide cold water line pressure
of 40 PSI. |
2. |
To properly adjust and provide for periodic
maintenance of the pressure reducing valve, a pressure gauge may be installed
between the pressure reducing valve and expansion tank. |
3. |
The entire piping system, including the pressure
reducing valve and gauge , must be protected against below freezing temperatures. |
4. |
The expansion tank must be installed no closer
than 18" to the water heater cold water inlet. |
5. |
The expansion tank is designed to be supported
by the system piping in a vertical position and this is the recommended
position. |
6. |
If the expansion tank must be installed horizontally,
it must be supported by adequate strapping. |