Web Page - Wire Size Chart For Submersible Pumps

TWO or THREE Wire Cable, 60 HZ
(Service Entrance to Motor - Maximum Length in Feet)
Motor Rating AWG Copper Wire Size
Volts
HP
14
12
10
8
6
4
3
2
1
0
2/0
3/0
4/0
115
1/3
130
210
340
540
840
1300
1610
1960
2390
2910
3540
4210
5060
1/2
100
160
250
390
620
960
1190
1460
1780
2160
2630
3140
3770
230
1/3
550
880
1390
2190
3400
5250
6520
7960
9690
11770
 
 
 
1/2
400
650
1020
1610
2510
3880
4810
5880
7170
8720
 
 
 
3/4
300
480
760
1200
1870
2890
3580
4370
5330
6470
7870
 
 
1
250
400
630
990
1540
2380
2960
3610
4410
5360
6520
 
 
1-1/2
190
310
480
770
1200
1870
2320
2850
3500
4280
5240
 
 
2
150
250
390
620
970
1530
1910
2360
2930
3620
4480
 
 
3
120
190
300
470
750
1190
1490
1850
2320
2890
3610
 
 
5
0
0
180
280
450
710
890
1110
1390
1740
2170
2680
 
7-1/2
0
0
120
200
310
490
610
750
930
1140
1410
1720
 
10
0
0
0
160
250
390
490
600
750
930
1160
1430
1760
15
0
0
0
0
170
270
340
430
530
660
820
1020
1260
1 Foot = .3048 Meter
CAUTION -- Use of wire size smaller than listed will void warranty.
Maximum lengths shown maintain motor voltage at 95% of service entrance voltage, running at maximum nameplate amperes.
This table is based on copper wire. If aluminum wire is used it must be two sizes larger. Example: When the table calls for #12 copper wire you would use #10 aluminum wire.
Single phase control box may be connected at any point of the total cable length.
Information Provided by Franklin Eletric


Home Page  |  Company Information

Last updated 02/13/2007